Explosion-proof light fitting for the illumination of indoor and outdoor industrial spaces with a danger of gas, vapour and dust explosion.
pro 591 44 01 II 2G Ex db eb op is IIC T5 Gb
II 2D Ex tb op is IIIC T90°C Db
pro 591 44 02 II 2G Ex db eb op is IIC T6 Gb
II 2D Ex tb op is IIIC T81°C Db
pro 591 44 03 II 2G Ex db eb op is IIC T5 Gb
II 2D Ex tb op is IIIC T87°C Db
Technical description:
A steel suspension with eye is fixed to the top part of the body. There are two cable outlets on the sides of the light fitting. The steel base plate with electrical equipment and reflector is built inside the light fitting. The light fitting is designed as a through light fitting, for two phase alternation (four-core cable). When the light fitting is used as a terminal light fitting, the free cable outlet is blinded with a plug.
Zone 1/21
Made in EU
Protection class
LED
Version
Voltage
Temperature
Degree of protection (IP)
Installation
Box
Emergency version
Luminaire body
Diffuser
Surface finish
Connection
Max. cable cross-section
Cable glands (material)
Cable glands (ø)
Lifetime
100.000 hours, L90B10
Driver functions
eCLo, ITG, IVG+, NFC, ETM+NTC, inputDIM
On request description
hade 154.5041/02, protective basket 2-99.6325, spanner 3-99.6159, blinding plug HSK-V-Ex, blinding plug HSK-V-Ex M20x1,5, screw plug V-Ex M25x1,5, screw plug V-Ex M20x1,5, screw plug V-Ms-VMQ-Ex M25x1,5, screw plug V-Ms-VMW-Ex M20x1,5, spanner 3-99.6159, flexible holder 2-99.5550
| Type | Power input [W] | Luminous flux [lm] | Luminous efficiency [lm/W] | Colour temperature [K] | Angle of beam [°] | CRI | Weight |
|---|---|---|---|---|---|---|---|
| 591 44 01 (K) | 100 | 15025 | 150 | 4000 (standard), 5000, 5700, 6500 | 120 | >80 | 15 |
| 591 44 02 (K) | 75 | 11475 | 153 | 4000 (standard), 5000, 5700, 6500 | 120 | >80 | 15 |
| 591 44 03 (K) | 65 | 9750 | 150 | 4000 (standard), 5000, 5700, 6500 | 120 | >80 | 14 |
| *By adding letter “K” behind type designation, light fittings will be provided with protective steel baskets (e.g. 591 44 02K). |
|---|
Maximum circuit breaker load and number of liminaires connected in series (half load for types 591 44 01, 591 44 02)
| Circuit breaker | C10 | C13 | C16 | C20 | B10 | B13 | B16 | B20 |
|---|---|---|---|---|---|---|---|---|
| Amount of luminaires max | 10 | 13 | 16 | 21 | 6 | 8 | 10 | 13 |
| Conductor cross-section | 1,5 | 1,5 | 2,5 | 4 | 1,5 | 1,5 | 2,5 | 4 |
| Starting current lmax | Time |
|---|---|
| 41.6A | 238us |
| *Actual values may vary due to the types of circuit breakers used and the installation environment. | |