Use: Explosion-proof light fitting for the illumination of indoor and outdoor industrial spaces with a danger of gas, vapour and dust explosion.
Technical description: The body and flange of the light fitting are AlSi alloy castings finished with RAL 1005 powder paint. The optical cover is made of tempered glass. A locking steel holder with eyes ø12.5 mm is fixed to the body. There are two cable outlets on the light fitting sides. There is electrical equipment and a reflector built inside the light fitting. The light fitting is designed as a through light fitting, for three-phase connection (five-core cable). When the light fitting is used as a terminal light fitting, the free cable outlet is blinded with a plug. The max. cross-section of the connecting conductors is 4 mm2.
Installation: With a steel suspension with eyes ø12.5 mm, using a wall holder 3-99.6183.
To order: Shade 154.5041/02, protective basket 1-99.5856, spanner 3-99.6159, blinding plug HSK-V-Ex M20x1.5, screw plug V-Ex M20x1.5, screw plug V-Ms-VMQ-Ex M20x1.5.
Downloads:
Type | Recommended light source [Q] | Temperature class | T max. of surface [°] | Voltage [V/Hz] | Weight / with basket [kg] |
---|---|---|---|---|---|
541 38 03 | High-pressure mercury discharge lamp HQL 250 | T5 | 87 | 230 / 50 | 26 / 27,5 |
541 38 03 | High-pressure sodium discharge lamp NAV-E/I 210 | T5 | 87 | 230 / 50 | 26 / 27,5 |
541 38 04 | High-pressure mercury discharge lamp HQL 400 | T3 | 135 | 230 / 50 | 27 / 28,5 |
541 38 04 | High-pressure sodium discharge lamp NAV-E/I 350 | T3 | 135 | 230 / 50 | 27 / 28,5 |
541 38 05 | High-pressure halide lamp HQI-E 250 | T4 | 105 | 230 / 50 | 26 / 27,5 |
541 38 05 | High-pressure sodium discharge lamp NAV-E 250 | T4 | 105 | 230 / 50 | 26 / 27,5 |
541 38 06 | High-pressure sodium discharge lamp NAV-E 400 | T3 | 135 | 230 / 50 | 27 / 28,5 |
541 38 07 | High-pressure halide lamp HQI-E 400 | T3 | 135 | 230 / 50 | 27 / 28,5 |
541 38 08 | High-pressure halide lamp HCI-TT 150 | T6 | 79 | 230 / 50 | 25 / 26,5 |
541 38 08 | High-pressure sodium discharge lamp NAV-E 150 | T6 | 79 | 230 / 50 | 25 / 26,5 |
541 38 03 t | High-pressure mercury discharge lamp HQL 250 | T4 | 102 | 230 / 50 | 26 / 27,5 |
541 38 03 t | High-pressure sodium discharge lamp NAV-E/I 210 | T4 | 102 | 230 / 50 | 26 / 27,5 |
541 38 04 t | High-pressure mercury discharge lamp HQL 400 | T3 | 230 / 50 | 27 / 28,5 | |
541 38 04 t | High-pressure sodium discharge lamp NAV-E/I 350 | T3 | 150 | 230 / 50 | 27 / 28,5 |
541 38 05 t | High-pressure halide lamp HQI-E 250 | T4 | 120 | 230 / 50 | 26 / 27,5 |
541 38 06 t | High-pressure sodium discharge lamp NAV-E 400 | T3 | 150 | 230 / 50 | 27 / 28,5 |
541 38 07 t | High-pressure halide lamp HQI-E 400 | T3 | 150 | 230 / 50 | 27 / 28,5 |
541 38 08 t | High-pressure halide lamp HCI-TT 150 | T5 | 94 | 230 / 50 | 25 / 26,5 |
541 38 08 t | High-pressure sodium discharge lamp NAV-E 150 | T5 | 94 | 230 / 50 | 25 / 26,5 |
541 38 05 Ft | High-pressure halide lamp HQI-E 250 | T4 | 120 | 230 / 50 | 26 / 27,5 |
541 38 05 Ft | High-pressure sodium discharge lamp NAV-E 250 | T4 | 230 / 50 | 26 / 27,5 | |
541 38 06 Ft | High-pressure sodium discharge lamp NAV-E 400 | T3 | 150 | 230 / 50 | 27 / 28,5 |
541 38 07 Ft | High-pressure halide lamp HQI-E 400 | T3 | 150 | 230 / 50 | 27 / 28,5 |