Explosion-proof light fittings zone 2/22

SIMPLEX

ELEKTROSVIT Svatobořice, a. s.

Ex logo II 3G Ex nR IIC T3-T6 Gc
zone 2/22 II 3D Ex tc IIIC T max. of surface Dc

Use: Explosion-proof light fitting for the illumination of indoor and outdoor industrial spaces with a danger of gas, vapour and dust explosion.

Technical description: The body and flange of the light fitting are AlSi alloy castings finished with RAL 1005 powder paint. The optical cover is made of tempered glass. There are two cable outlets on the light fitting sides. There is electrical equipment and a reflector built inside the light fitting. The light fitting is designed as a through light fitting, for three-phase connection (five-core cable). When the light fitting is used as a terminal light fitting, the free cable outlet is blinded with a plug. The max. cross-section of the connecting conductors is 4 mm2.

To order: Ballast box BOX 2 for fitting with a discharge lamp, shade 254.5021/01, protective basket 2-99.6195, ceiling holder 4-99.7995, flexible suspension 2-99.5550, blinding plug HSK-V-Ex M20x1.5, screw plug V-Ex M20x1.5, screw plug V-Ms-VMQ-Ex M20x1.5.

Downloads:

Type Recommended light source [W] Temperature class T max. of surface [°C] Voltage [V/Hz] Weight [kg]
511 14 07 n Halogen bulb Philips EcoClassic 140 T4 108 230 / 50 5
511 14 07 n Bulb CLAS 200 T4 104 230 / 50 5
511 14 07 n Blended lamp HWL 160 T4 99 230 / 50 5
511 14 07 n **High-pressure mercury discharge lamp HQL 80 T5 95 230 / 50 5
511 14 07 n ***High-pressure mercury discharge lamp HQL 125 T4 121 230 / 50 5
511 14 07 n Compact fluorescent tube DULUX EL 23 T6 59 230 / 50 5
511 14 07 nFt Halogen bulb Philips EcoClassic 140 T4 118 230 / 50 5
511 14 07 nt Bulb CLAS 200 T4 114 230 / 50 5
511 14 07 nt Blended lamp HWL 160 T4 109 230 / 50 5
511 14 07 nt **High-pressure mercury discharge lamp HQL 80 T4 105 230 / 50 5
511 14 07 nt ***High-pressure mercury discharge lamp HQL 125 T3 131 230 / 50 5
511 14 07 nt Compact fluorescent tube DULUX EL 23 T6 69 230 / 50 5
511 14 07 nSt Bulb (DC) 100 T4 100 24-230 DC 5
511 14 07 nSt Compact fluorescent tube DULUX EL FACILITY 18 T6 69 230 DC 5
511 14 07 nS Bulb NARVA AGM 60 T5 90 110 DC 5
511 14 07 nF Halogen bulb Philips EcoClassic 140 T4 108 230 / 50 5
511 14 07 nF Bulb CLAS 200 T4 104 230 / 50 5
511 14 07 nF Blended lamp HWL 160 T4 99 230 / 50 5
511 14 07 nF **High-pressure mercury discharge lamp HQL 80 T5 95 230 / 50 5
511 14 07 nF ***High-pressure mercury discharge lamp HQL 125 T4 121 230 / 50 5
511 14 07 nFt Halogen bulb Philips EcoClassic 140 T4 118 230 / 50 5
511 14 07 nFt Bulb CLAS 200 T4 114 230 / 50 5
511 14 07 nFt Blended lamp HWL 160 T4 109 230 / 50 5
511 14 07 nFt **High-pressure mercury discharge lamp HQL 80 T4 105 230 / 50 5
511 14 07 nFt ***High-pressure mercury discharge lamp HQL 125 T3 131 230 / 50 5
*By adding letter "K" behind type designation, light fittings will be provided with protective steel baskets (511 14 07 nK
**Light fitting provided with a mercury discharge lamp HQL 80W requires a ballast box type 604.6 ntB
***Light fitting provided with a mercury discharge lamp HQL 125W requires a ballast box type 604.6 ntA