Array

ES PROTEC EX

ELEKTROSVIT Svatobořice, a. s.

Ex logo II 3G Ex  ec IIC T4 Gc
Zone 2/22 II 3D Ex tc IIIC T70°C IP66/67 Db

Use: Explosion-proof light fitting for the illumination of indoor and outdoor industrial spaces with the danger of gas, vapur and dust explosion.

Technical description: The body and the diffuser are made of polycarbonate. The optical cover is fixed by eight stainless steel clamps. The max. cross-section of the connecting conductors is 2,5mm2.

Instalation: On the ceiling, pipe or on the wall with use of mounting brackets.

Versions: A3 version of light fitting is equiped with internal power supply module capable of continuous work in emergency mode, for at least three hours, in case of mains failure. Ambient temperature for each emergency version: 0°C up to +45°C. Standard light fittings are available with polyamide cable outlets M20x1,5, optionally with polyamide cable outlets M25x1,5 or metal cable glands M20x1,5 or M25x1,5.

To order: standard mounting bracket, angle (45°) mounting bracket, distance (type C) mounting bracket, mounting bracket for a pipe

Downloads:

Type Power input [W] Efficiency [lm/W] Luminuous flux [lm] Dimensions [mm]
ES PROTEC EX -S-1 18 136 2470 673 x 190  x 134
ES PROTEC EX-S-2 26 132 3441 673 x 190 x 134
ES PROTEC EX-M-1 35 140 4940 1283 x 190 x 134
ES PROTEC EX-M-2 51 134 6882 1283 x 190 x 134
ES PROTEC EX-L-1 44 140 6176 1583 x 190 x 134
ES PROTEC EX-L-2 60 135 8603 1583 x 190 x 134
*By adding letter „M“ behind type designation, light fittings will be provided with metal cable glands. *By adding letter „P“ behind type designation, light fittings will be provided with polyamide cable glands. *By adding number 10 behind type designation, light fittings will be provided with one cagle gland on one side of light fixture, without a cross wiring. *By adding number 11 behind type designation, light fittings will be provided with two cable glands on both sides of light fixture, with a cross wiring. *By adding number 20 behind type designation, light fittings will be provided with two cable glands on one side of light fixture, power supply cables can be bridged in connection terminal. *By adding number 22 behind type designation, light fittings will be provided with four cable glands, two on both sides of light of light fixture, with a cross wiring. *E.g. ES PROTEC EX-S-1-P20 – light fittings will be provided with two cable glands on one side of light fixture, power supply cables can be bridged in connection terminal.